95. Subject to the restrictions in the second paragraph, the following types of flow control devices must be used:
(1)  orifice or orifice plate;
(2)  flow restricting pipe;
(3)  broad-crested or sharp-crested weir;
(4)  vortex flow regulator;
(5)  buoyant flow control devices providing a constant discharge.
Except in the case of peak flows equal to or less than 15L/s, vortex flow regulators or buoyant flow control devices providing a constant discharge may not be used in a dry retention system to reproduce peak flows with a period equal to or less than 25 years.
O.C. 871-2020, s. 95.